Cable Distribution Cabinet
The cable distribution cabinet adopts component module assembly and frame assembly structure, and the bus and feed out are insulated enclosed.
Five structural types can be adopted:
1. The incoming line adopts insulated enclosed disconnector, and the outgoing line adopts MCCB;
2. The incoming line adopts insulated enclosed disconnector, and the outgoing line adopts knife fuse switch;
3. The incoming line adopts strip disconnector and the outgoing line adopts strip switch (with fuse protection);
4. The incoming line does not have a switch, and the outgoing line adopts a knife melting switch;
5. The incoming and outgoing lines are not equipped with switches.
Executive standard
IEC269 Low voltage fuse
IEC282/1 Current limiting circuit breaker
IEC517 Rated voltage 1kv~ 36kv High Voltage AC and control insulation
IEC439 Low voltage switchgear and control equipment package
IEC144-63 Protection level of enclosures of low voltage switchgear and control equipment
IEC364.3.1 Electrical equipment of buildings Part 3 "General requirements for installation equipment" chapter I safety
Service Environment
No | Item | Unit | Guarantee Value | |
1 | Ambient air | Max air temperature | ℃ | +45 |
Min air temperature | -25 | |||
Max daily temperature | K | 30 | ||
2 | Altitude | m | ≤1000 | |
3 | Humidity | Average daily relative humidity | % | ≤95 |
Average Monthly relative humidity | ≤90 | |||
4 | Earthquake resistance (horizontal acceleration) | m/s2 | 0.2g |
Technical Data
No | Name | Item | Unit | Technical data |
One | General technical data | |||
1 | Enclosure | Installation | Outdoor/Indoor | |
Enclosure Material | S304 Stainless steel | |||
Protection Level | IP44 | |||
Measurement | See the drawing | |||
2 | Bus-bar | Rated working Voltage | V | 400 |
Rated frequency | Hz | 50 | ||
Rated current | A | 630 | ||
Rated insulation voltage | V | 660 | ||
Rated short-circuit withstand current | 10kA, 1S | |||
Bus-bar Material | Copper | |||
Two | The incoming line adopts insulated enclosed disconnector, and the outgoing line adopts MCCB; | |||
1 | MCCB | Number of poles | 3P | |
Release type | Electronic | |||
Rated working Voltage | V | 400 | ||
1 | MCCB | Rated insulation voltage | V | 660 |
Rated current | A | 250/160 | ||
Rated short-circuit withstand current | kA | 10 | ||
Rated ultimate breaking capacity | kA | 50 | ||
2 | Disconnector | Rated short-circuit withstand current | 10kA, 1S | |
Rated current | A | 400/630 | ||
Rated working Voltage | V | 400 | ||
Rated insulation voltage | V | 660 | ||
Number of poles | 3P |